TM 55-1925-283-12&P
0006 00
OPERATING THE FUEL FILTER/WATER SEPARATOR WITH NO ELECTRICAL POWER
! CAUTION
Only one fuel transfer pump at a time may be operated while using the fuel filter/water
separator. Attempting to use two fuel transfer pumps will exceed the capacity of the fuel
filter/water separator and could result in damage to the fuel filter/water separator or to
the fuel transfer pumps.
NOTE
The fuel filter/water separator is capable of normal operation without electrical power.
However, the fuel filter/water separator's sump must be frequently checked for water
1. Line up the fuel transfer system's valves to fill the desired tank (TM 55-1925-273-10).
2. At the 120V emergency distribution panel No. 1, set the RACOR FILTER circuit breaker (figure 2, item 1) to
the OFF position.
1
ENGINE ROOM EMER
DIST PANEL NO. 1
Figure 2. 120V Emergency Distribution Panel No. 1
0006 00-2