TM 55-1925-284-14&P
0014 00
1
Figure 1. MSD Wet Well
3. Fill a suitable sample bottle with the effluent from the WET WELL SAMPLE valve MSD-11(figure 1, item 1).
4. Using the sanitizer test kit, dip a chlorine test strip into the sample effluent and move the strip back and forth
for 30 seconds.
5. Read the total chlorine level on the sample strip. An acceptable reading will register between 1.0 and 2.0
parts per million (ppm) of total chlorine.
6. If a reading of 0.0 ppm is indicated, take another sample and compare the two readings. If the sample is
below 1.0 ppm, adjust the chlorinator to provide more chlorine (WP 0013 00).
7. If the sample is above 2.0 ppm, adjust the chlorinator to provide less chlorine (WP 0013).
0014 00-2