TO 40R7-5-10-1
3-35. TEST MALE RECEPTACLE.
TOOLS: Digital Multimeter
NOTE
PROCEDURE
1. With multimeter, perform isolation testing across the two plug terminals, and across each plug terminal and the
ground terminal or receptacle case. Multimeter shall indicate infinite resistance across both plug terminals and
across each plug terminal and the ground terminal. Otherwise, receptacle is defective and shall be replaced.
NOTE
3-41