36
Monthly
Inspect the solenoid valves for frayed or broken
Wire lead frayed or
Valves
wire leads, loose coil, loose or missing cover, and
broken, coil loose, or
evidence of refrigerant leak. If coil is loose or
evidence of leak is found.
damaged or wire leads are frayed or broken,
notify unit maintenance to repair or replace it as
necessary. If evidence of leaking found, notify
direct support maintenance to replace it.
37
Monthly
Flare
Evidence of leak is found.
refrigerant leak. If evidence of leaking found,
notify direct support maintenance to tighten or
replace them as necessary.
38
Monthly
Accumulator
Inspect the accumulator for damage and
Accumulator is damaged
evidence of refrigerant leak. If damaged or
or evidence of leak is
evidence of leaking found, notify direct support
found.
maintenance to replace it.
39
Monthly
Tubing and
Inspect the tubing and fittings for kinks,
Tubing or fittings
Fittings.
restriction (crushed), or evidence of refrigerant
damaged, kinked, or
leak. If damaged or evidence of leaking found,
evidence of leak is found.
notify direct support maintenance to repair or
replace it as necessary.
40
Monthly
Pressure
Inspect the pressure switches for frayed or
Wire lead frayed or
Switches
broken wire leads and dented, loose, or missing
broken, cover missing, or
cover. Inspect for evidence of refrigerant leak.
evidence of leak is found.
If cover is loose or wire leads are frayed or
broken, notify unit maintenance to repair or
replace it as necessary. If damaged or evidence
of leaking found, notify direct support
maintenance to replace it.