TM 9-4110-256-14
d. Installation.
(1)
Install three new thermal overload heaters (6) onto new motor starter (5).
NOTE
Steps 2 through 4 apply only to new motor starter. A new motor starter is configured with jumpers
connected for operation at 115 Vac and must be reconnected for use with 208/230 Vac.
(2)
Remove two red wire lead jumpers between terminals L2 to 96 and Al to 3. Discard jumpers.
(3)
Move red wire lead jumper from between terminals A2 to 95 and place between terminals Al to 95.
(4)
Set overload adjustment (FLA) dial to A position and (RESET) adjustment dial to M position.
(5)
Install motor starter (5), flat washer (14), new lock washer (13), and bolt (12).
(6)
Install flat washer (11), new lock washer (10), and screw (9).
(7)
Using tags and wiring diagram (fig. 1-4), install wire leads (8). Remove tags.
(8)
Close control box cover (3). Install two new lock washers (2) and bolts (1).
NOTE
FOLLOW-ON MAINTENANCE:
Close control panel cover.
Connect power and put unit back into service.
4-49