5-16. ACTUATING CYLINDERS AND CONDENSER AIR OUTLET DAMPER LINKAGE (MODELS F36T 2SA AND
F36T4 2SB ONLY) - Continued.
(6) It the actuating cylinder is to be replaced by a new one, the connector bracket may be removed by drilling
out the three rivets using a drill and a bit slightly smaller than the rivet body.
c.
Installation
If a new actuating cylinder is being installed, secure connector bracket to cylinder end with three rivets.
(1)
Position actuating cylinder and insert mounting studs through bracket.
(2)
(3)
Using wrench, secure cylinder to bracket with two lock nuts.
(4)
Using wrench, connect and tighten flare nut.
(5)
Using wrenches, secure the connector bracket to the two damper controls with the two sets of hardware
that consists of tour nuts and two cap screws.
(6)
(7)
Leak test all newly connected joints and those in the repair area. (See para 5-10.)
(8)
(9)
Using wrench, secure condenser motor channel support with eight cap screws.
Install actuating cylinder access cover. (See para 4-20.)
Follow-on procedure:
5-17. LOW PRESSURE CUTOUT SWITCH (S6)
Preliminary procedures:
1. On F36T2SA and F36T42SB remove condenser discharge air deflector door (See
2. Pull safety control box out far enough to gain access to panel mounting screws. (See