TM 9-4120-371-14
(7)
Insert sensing bulb into its mounting loop clamps in its original position, and tighten the screws
and nuts. Be sure sensing bulb is installed in the original position and is making good metal-to-metal contact
with suction line.
Reinstall insulation tubing with tape, item 11, Appendix E.
(8)
(9)
(10) Leak test all newly connected joints and those in the repaired area. (See para 5-9.)
(11) Evacuate and charge the refrigerant system. (See para 5-10 and 5-11.)
Follow-on procedure: Install junction box. (See para 4-47.)
Preliminary procedures: 1. Remove junction box. (See para 4-47.)
2. Remove side access plate. (See para 422.1.) (Keco Model FI 8T-2S Serial
No.82760 and higher, Keco Model F18T-2SA, and A.R.E. Model CVP-20-5/6-08.)
The compressor and motor assembly are hermetically sealed in a metal canister and are not repairable. The
following items may be replaced without opening the refrigerant pressure system:
Z Connector (J4)
Heater
Heater thermostat
**Effective for Keco Compressor