Section IV. REMARKS MAINTENANCE ALLOCATION CHART - Continued
Reference
Remarks
Code
AU
Replace fusible plug
AV
Apply gas pressure to verify actuator operation
AW
Braze valve adapter and tube fitting to replacement item
AX
Braze external tubing
AY
Replace knob
AZ
Remove cable entry panel box for access
BA
Straighten damaged fins with fin comb and vacuum
BB
Adjust linkage for damper operation
BC
preventative as required
BD
Clean and vacuum drain pan and/or drain holes
BE
Drill (3) 5/32-inch holes through terminals of replacement Item
BF
Adjust low refrigerant pressure switch to close @ 20 psig 5 and open @ 40 psig 5
Adjust high refrigerant pressure switch to close @ 450 psig 25 and open @ 360 psig 25
B-15