TM9-4120-401-14
LOGIC BOX ASSEMBLY (LGC1). - continued
5-8.
4 LED 7 illuminates for 2 seconds and then turns off for 2 seconds.
5 LED 7 shall illuminate. End of routine.
(i)
Place S6 in the ON position for 2 seconds and then place S6 in the OFF position. The following
routine shall occur:
1 LED 7 shall remain illuminated.
2 For the next 8 seconds: LED 6 illuminates. LED 7 remains illuminated.
3 For the next 2 seconds: LEDs 6 and 7 turn off.
4 LED 7 illuminates for 2 seconds and then turns off for 2 seconds.
5 LED 7 shall illuminate. End of routine.
Place S1 in the ON position for 2 seconds and then place S1 in the OFF position. LED 7 shall turn
(j)
off for 10 seconds and then illuminate.
(k) Place S1 in the ON position. LED 7 shall turn off and in 10 seconds LED 3 shall illuminate.
Place S1 in the OFF position and reset MODE switch by turning to OFF/RESET. Turn MODE switch
(l)
back to VENT position. In 2 seconds LED 7 illuminates.
(m) Place S7 in the OFF position: place S4. S5, and S6 in the ON position. Place S1 in the ON position
and in 2 seconds place S7 in the ON position. LED 7 shall turn off and in 10 seconds LED 3 shall
illuminate. S4, S5, and S6 have no effect.
(n) Place switches S1 through S6 in the OFF position. Reset by turning MODE switch to OFF/RESET
and then back to VENT. Place S7 in the OFF position: place S4, S5, and S6 in the ON position.
Place S7 in the ON position and in 1 second place S1 in the ON position. LEDs 4,5, and 6 shall
illuminate. After S1 is turned ON LEDs 4, 5, and 6 turn off. After 10 seconds LED 3 illuminates and
LED 7 is off.
(o) Reset by turning MODE switch to OFF/RESET position however, do not change any other switch
positions. No LEDs are illuminated but in 10 seconds LED 3 shall illuminate.
(5) Cool mode test.
(a) Place switches S1 through S6 in the OFF position and AMBlENT control to mid range. Reset by
turning MODE switch to OFF/RESET position and then to COOL position. Rotate TEMPERATURE
control to COOL position. After a 2-second delay LEDs 2 and 7 shall illuminate.
(b) Slowly rotate TEMPERATURE control to the WARM position until LED 2 just turns off. LED 7 shall
remain illuminated.
(c) Slowly rotate AMBIENT control toward the WARM position. LED 7 shall turn off. After 2 seconds
LEDs 2 and 7 shall illuminate.
(d) Rotate AM BlENT control to COOL position. Rotate TEMPERATURE control to COOL position.
Place S4 in the ON position. The following routine shall occur:
1 LED 2 shall turn off and LED 7 shall remain illuminated.
5-18