TM 9-4120-407-14
c. Connecting Control Cable. This procedure is used only if the control panel has been remote mounted.
(2) Connect the appropriate end of control cable to the control panel.
(3) Route control cable to the air conditioner through the return air opening or lower front panel as
appropriate and connect.
d. Preparing Drains.
NOTES
The air conditioner is provided with eight drain holes in the
base.
Any type of hose or tubing may be used as a drain line.
(1) Remove plugs from as many drains as possible.
(2) If a drain line is required, install standard l/2-14 NPT male pipe fittings into drains to connect
hose or tubing. Route the drain line to an appropriate facility drain, storm sewer, dry sump, or an
acceptable outside area while keeping the entire length at or below the air conditioner base
height.
3-11