TM 9-4120-407-14
Table 3-2. Unit Preventive Maintenance Checks and Services for Model F36T-MPI - Cont
Location
Not Fully Mission Capable
Item To
Procedures
Interval
Item
if:
Check/Service
No
Condenser Fans -
25
Annually
for any reason and are dirty,
Cont
clean them per the
following:
(1) Mix a small quantity of
detergent
clean water to make a wash
solution.
(2) Dampen a rag
wash solution and clean the
condenser fans. Carefully use
a scrub brush
remove any caked on dirt or
deposits.
(3) Dampen a rag with clean
water and rinse the
condenser fans. Rinse rag in
clean water and continue
until all detergent residue
has been removed.
(4) Wipe the condenser fans
with a clean dry rag.
Install the condenser fan cover
assemblies per
Check condenser fan motor (1) for Condenser fan motor is
Condenser Fan
26
Annually
any visible damage such as
damaged.
Motor
dented or cracked housing
and burns or other evidence
of overheating. Check that
shaft turns smoothly with no
binding or looseness. Check
wire leads for any visible
damage such as broken wires,
loose connection, and cut or
frayed end. Test or replace
3-40