Home
Download PDF
Order CD-ROM
Order in Print
Chapter 1 General Information, Equipment Description, and Theory of Operation - TM-55-1925-285-13-P0015
MAINTENANCE FORMS, RECORDS, AND REPORTS - TM-55-1925-285-13-P0017
LIST OF ABBREVIATIONS/ACRONYMS - TM-55-1925-285-13-P0018
QUALITY OF MATERIAL - TM-55-1925-285-13-P0019
EQUIPMENT CHARACTERISTICS, CAPABILITIES, AND FEATURES - TM-55-1925-285-13-P0021
Figure 1. OCM and OWS Major Component Locations (Plan View)
Figure 2. OCM and OWS Major Component Locations (Profile View)
DIFFERENCES BETWEEN MODELS - TM-55-1925-285-13-P0024
Table 1. Oil Water Separator Technical Characteristics
Figure 1. Normal Processing Mode
Table 1. Approved Short-Lived Detergents for Bilge Cleaning
OIL DISCHARGE
Figure 3. Oil Content Monitor System, Block Diagram
Figure 4. Nozzle Sampler, General Arrangement
Figure 5. Sample and Detection Subassembly (SDA)
Figure 6. Sampling/Sensor Assembly
REMOTE INDICATOR (ALARM) ASSEMBLY
Figure 7. Remote Indicator (Alarm) Assembly, External
REMOTE RELAY ASSEMBLY
OCM PRINCIPLE OF OPERATION
CHAPTER 2 Operator Instructions - TM-55-1925-285-13-P0039
Figure 1. Oil Water Separator (OWS) and Oil Content Monitor (OCM), Engine Room
Table 1. Oil Water Separator (OWS) and Oil Content Monitor (OCM), Engine Room (refer to figure 1)
Table 1. Oil Water Separator (OWS) and Oil Content Monitor (OCM), Engine Room (refer to figure 1) - CONT
Figure 2. OCM Sampling/Sensor Assembly
Table 2. OCM Sampling/Sensor Assembly (refer to figure 2)
Table 3. Remote Indicator (Alarm) Assembly (refer to figure 3)
OPERATING PROCEDURES - TM-55-1925-285-13-P0047
Figure 2. 120V Distribution Panel No. 4 - TM-55-1925-285-13-P0048
Figure 3. OWS, OB, and OCM Piping - TM-55-1925-285-13-P0049
Table 1. Valve Positions During Operation Under Usual Conditions
Figure 4. Sampling/Sensor Assembly Interior - TM-55-1925-285-13-P0051
Figure 5. OCM Diverter Valve Position Indicator
Figure 6. Remote Indicator (Alarm) Assembly
Figure 7. Sampling/Sensor Assembly Indicators
OPERATING PROCEDURES - TM-55-1925-285-13-P0055
OWS SHUTDOWN - TM-55-1925-285-13-P0056
UNUSUAL OPERATING CONDITIONS
Figure 1. OWS Control Panel
Figure 2. 120V Distribution Panel No. 4 - TM-55-1925-285-13-P0059
Figure 3. OWS, OB, and OCM Piping - TM-55-1925-285-13-P0060
Table 1. Valve Positions During OCM Operation In Test Mode
Figure 4. Sampling/Sensor Assembly Interior - TM-55-1925-285-13-P0062
OWS SHUTDOWN - TM-55-1925-285-13-P0063
Figure 6. OWS, OB, and OCM Piping
Table 2. Valve Positions For Manual Backflush During Operation Under Unusual Conditions
MANUAL BACK FLUSH SHUTDOWN
CHAPTER 3 Troubleshooting Procedures - TM-55-1925-285-13-P0067
USE OF TROUBLESHOOTING PROCEDURES
Table 1. Operator Troubleshooting Preocedures
Table 2. Unit Troubleshooting Procedures - TM-55-1925-285-13-P0071
INTRODUCTION - TM-55-1925-285-13-P0073
Procedure 1. OCM Has No Power
Procedure 2. OCM Will Not Start
Procedure 3. OWS Control Panel Has No Power
Procedure 4. OWS Pump Will Not Start (Sheet 1 of 2)
Procedure 4. OWS Pump Will Not Start (Sheet 2 of 2)
Malfunction/Symptom - TM-55-1925-285-13-P0079
Procedure 1. Vacuum Unusually High During Normal Processing
Procedure 2. Vacuum Unusually Low During Normal Processing
Procedure 3. OWS Pump Deadheaded
Procedure 4. Low Or No Effluent Discharge (Sheet 1 of 2)
Procedure 4. Low Or No Effluent Discharge (Sheet 2 of 2)
Procedure 5. High Oil Content In Effluent
Procedure 6. OWS Relief Valve Opens Or Fails To Reseat
Procedure 7. OWS Fails To Operate In MAN Mode (Sheet 1 of 2)
Procedure 7. OWS Fails To Operate In MAN Mode (Sheet 2 of 2)
Procedure 8. Frequent Oil Discharge
Procedure 9. Oil Does Not Discharge (Backflush) From OWS (Sheet 1 of 2)
Procedure 9. Oil Does Not Discharge (Backflush) From OWS (Sheet 2 of 2)
Procedure 10. Pump Noisy
Procedure 11. OCM POWER ON Indicator Does Not Light (Sheet 1 of 3)
Procedure 11. OCM POWER ON Indicator Does Not Light (Sheet 2 of 3)
Procedure 11. OCM POWER ON Indicator Does Not Light (Sheet 3 of 3)
Figure 1. OCM Sampling/Sensor Assembly Wiring Diagram
Procedure 12. OCM WARNING 1 (Red LED) Lit
Procedure 13. OCM WARNING 2 (Red LED) Lit
Procedure 14. OCM WARNING 3 (Red LED) Lit
Procedure 15. OCM WARNING 2 And WARNING 3 (Red LEDs) Lit
Procedure 16. Unstable Oil Content Display, PPM Valves Jump High, Then Low
Procedure 17. OWS Discharge Is Diverted Inboard When OCM Detects Less Than Alarm Limit
Figure 2. Sampling/Sensor Assembly, Power PCB Jumper Installation
Procedure 18. Remote Indicator (Alarm) Assembly Indicators Inoperative While OCM Is Operating
Figure 3. Remote Indicator (Alarm) Assembly
Procedure 19. PUSH TO CHANGE ALARM LIMIT Switch A2S1 Does Not Change Alarm Limit Of OCM
Procedure 20. Audible Alarm Inoperative When OCM Is In ALARM Mode (Sheet 1 of 2)
Procedure 20. Audible Alarm Inoperative when OCM Is In ALARM Mode (Sheet 2 of 2)
Procedure 21. Diverter Solenoid Valve Works Opposite To Intended Control Function
CHAPTER 4 Maintenance Instructions - TM-55-1925-285-13-P0111
SERVICE UPON RECEIPT AND PREPARATION FOR STORAGE - TM-55-1925-285-13-P0113
ITEM NUMBER COLUMN
LEAKAGE CLASSIFICATIONS I, II, III - TM-55-1925-285-13-P0116
INSPECTION - TM-55-1925-285-13-P0117
OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES INCLUDING LUBRICATION - TM-55-1925-285-13-P0119
OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES INCLUDING LUBRICATION - TM-55-1925-285-13-P0120
OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES INCLUDING LUBRICATION - TM-55-1925-285-13-P0121
OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES INCLUDING LUBRICATION - TM-55-1925-285-13-P0122
TM-55-1925-285-13-P Oil Water Separator Inland and Coastal Large TUG (LT) NSN
1925-01-509-7013
(EIC XAG) Manual
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business