TM 55-1925-285-13&P
0009 00
Opposite to Intended Control Function
Warning:
Take great care when working around energized
electrical equipment. Contact between
unprotected body parts and electrical conductors
can cause serious injury.
Verify jumper plugs are in first B
(figure 2, item 1) and second A
(figure 2, item 2) positions.
Does
Are the
the valve
Yes
No
Properly install
operate
properly
properly?
installed?
No
Yes
Warning:
Take great care when working around energized
electrical equipment. Contact between
unprotected body parts and electrical conductors
can cause serious injury.
Is 115 Vac
present across
Is OCM
Yes
Yes
Replace the power
terminals 2 and
in ALARM?
PCB (WP 0016 00).
3 on the power
PCB (figure 1,
item 3)?
No
Notify
maintenance
No
supervisor.
Exit
is defective. Notify
maintenance supervisor.
Procedure 21. Diverter Solenoid Valve Works Opposite To Intended Control Function
END OF WORK PACKAGE