Table 4-2. TROUBLESHOOTING (Cont.)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4. COMPRESSOR STARTS NORMALLY, BUT HIGH OR LOW PRESSURE CUT-OUT SWITCH SOON
TRIPS.
Step 1. Check to be sure fabric cover is rolled up.
Roll up and secure fabric cover.
Step 2. Check to be sure there is no restriction to air flow through condenser section.
Clean all obstructions from condenser inlet, outlet, and condenser coil.
CONDENSER AIR O U T L E T
C O N D E N S E R AIR INLET
Step 3. Check to be sure that condenser fan is operating. (Air being discharged from condenser air
outlet.)
NOTE
one fan is operating and the other is not, check for loose fan on motor shaft. If both fans
are not operating, check for loose electrical connections, defective motor relay (K4), or
defective motor (B2).
4-47