ARMY TM 9-4120-380-14
NAVY EE-000-BA-MMA-010/7053-AC
AIR FORCE TO 35E9-136-21
Table 4-2. Unit Maintenance Troubleshooting - Continued
Malfunction
Test or Inspection
Corrective Action
10.
FAULT RESET SWITCH (S12) DOES NOT RESET
Disconnect input power before performing internal electrical troubleshooting. Voltages used
can KILL.
Step 1. Check operation of reset switch (S12).
Step 2. Check operation of latching relay (K11).
Step 3. Check operation of latching relay (K11) 11-pin socket.
11.
DIRTY FILTER LIGHT (DS5) ON
Step 1. Check return air filter.
Step 2. Check operation of dirty filter relay (K7).
Step 3. Check operation of relay (K7) 11-pin socket..
Step 4. Check operation of dirty filter slave relay (K13).
Step 5. Check operation of airflow filter switch (S3).
4-26