Remarks
Code
Y
Cut terminal track to required length on replacement part (TB1)
Z
AA
Perform the following alterations on replacement motor Cut leads to 5 Inches, strip and dead end
wires together for 208 Vac, 3-phase operation Add corrosive prevention compound to both shafts
MIL-C-85054 (as) clear
AB
Perform the following alterations to replacement evaporator (circulator) and condenser fan housing
(left, right hand) Enlarge (5) 9/64-inch holes to 13/64 diameter and paint
AC
Paint replacement inlet flange
AD
Replace electrical connector
AE
Substitute cast iron hardware on replacement part with stainless steel
AF
Adjust thermostat to nominal 80 degrees F
AG
Adjust pressure to 1.15 inches WC
AH
Adjust thermostat to nominal 110 degrees F
Al
When replacing crankcase heater, perform the following alterations Cut leads to 16 inches long and
strip ends back to 1/2 inch maximum Coat heating element with thermal grease
AJ
Tighten sight glass if leak Is detected
AK
Cut off one swedged end (either end) of replacement sight glass to shorten overall length to 5 inches
AL
Replace gasket
AM
Replace grommet
AN
Remove one knockout from replacement Item
AO
Strip and dead end wires when installing replacement part
AP
Install and crimp pig tails to wires
AQ
Replace entire assembly on failure
AR
Raise/lower superheat setting
AS
Replace cage assembly and/or power head assembly
AT
Adjust for valve response rate and/or suction pressure