TM 9-4120-399-14
Table 5-1. Direct Support Troubleshooting. (Continued).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
DISCHARGE PRESSURE TOO HIGH. (Continued).
1.
Step 2. Check for refrigerant overcharge.
Step 3. Check sight glass for air in refrigerant system.
Step 4. Check operation of condenser fan motor.
Step 5. Check to see if condenser fan is loose on shaft.
Step 6. Check to see if there is too much oil in the refrigerant system.
DISCHARGE PRESSURE TOO LOW.
2.
Step 1. Check too see that cold outside air is not entering the room.
Step 2. Check sight glass for low refrigerant charge.
Step 3. Check pressure regulating valve.
5-2