TM 9-4120-402-14
1-8. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS. - continued
CONDENSER COIL (22). Multiple tube, finned coil. As air is circulated over the coil it allows heat to be removed from
the compressed refrigerant vapor so it will condense into a liquid.
CONDENSER COIL GUARD (23). Protects the condenser coil from damage.
CONDENSER FAN (24). This fan draws outside air over the condenser coil to remove heat from the refrigerant flowing
through it.
FAN MOTOR (25). Drives both the conditioned air (evaporator) fan and the condenser fan.
1-9.
DIFFERENCES BETWEEN MODELS.
There are no model differences in effect on the Keco Model F18T-MPI air conditioner.
1-10. EQUIPMENT DATA.I
AMBIENT OPERATING TEMPERATURE RANGE
LOW
-50 (-45 )
F
C
HIGH
+120 (+49 )
F
C
PERFORMANCE
COOLING CAPACITY
18,500 BTU/HR
12,000 BTU/HR
POWER REQUIRED
VOLTAGE
208
PHASE
3
HERTZ
50/60 or 400
FULL LOAD AMPERAGE
18
DIMENSIONS
WIDTH
17.25 inch (43.78 cm)
DEPTH
21.60 inch (54.85 cm)
HEIGHT
45.78 inch (116.28 cm)
WEIGHT
265 pounds (120.2 kg)
REFRIGERANT
TYPE
R-22
CHARGE
3.4 pounds (1.5 kg)
1-5