TM 9-4120-407-14
1-11. EQUIPMENT DATA.
OPERATING TEMPERATURES
L o w.................................................................. -50 F (-148 C)
H i g h ............................................................. 120 F (158 C)
PERFORMANCE
Cooling Capacity ............................................. 36,000 Btu/Hr
Heating Capacity ............................................ 28,600 Btu/Hr
POWER REQUIREMENTS
Voltage ............................................................................ 208
P h a s e .............................................................................
3
Hertz .................................................................... 50/60 or 400
Full Load Amperage .......... 37 (average between three phases)
Number of Conductors ........................................................... .5
DIMENSIONS
W i d t h . . ..................................................... 30.80 in. (78.32 cm)
Depth.. ...................................................... 20.00 in. (50.80 cm)
H e i g h t ..................................................... 55.06 in. (139.85 cm)
Weight ........................................................... 470 lbs. (213 kg)
REFRIGERANT
Type ................................................................................. R-22
Charge ............................................................. 6.2 lbs (2.8 kg)
R a t e................. 1250 cfm (35 m3/m) at 0 in (0 cm) water gauge
1-7