TM 9-4910-663-12
h.
Use of DC Generator for Starter Testing.
(1) It is possible to provide dc power for free running starter
tests by means of a dc aircraft type generator, driven by output shaft
(1, 3, fig 1-2) of varidrive. Cooling air for generator must be
supplied by external blower. Proceed as follows:
CAUTION
Depending upon voltage and current rating of
starter under test, it may be necessary to use
generator of corresponding output voltage. In
some instances, it will be possible to use a 24
volt generator for lower voltage starter tests by
dropping output voltage through adjustment of a
regulator, speed of generator, and setting of
starter rheostat on test stand.
proper output shaft (1, 3, fig 1-2) by means of splined coupling and
adapter (6, 5, fig 2-9). Then, terminals of generator and its asso-
ciated regulator are connected through test stand circuitry to provide
field current control by means of FIELD CURRENT 0-5 AMPS (MAX) control
(R27, fig 2-2). Connect generator (+) to STARTER INPUT binding post
(fig 2-3) and generator (-) to GENERATOR G- binding post. A jumper
link must be installed between REGULATOR B- binding post and REGULATOR
G- binding post. Install a jumper between starter input and GENERATOR
G+ binding post.
NOTE
Before operating generator, make certain that
POLARITY REVERSING SWITCH (S7, fig 2-2) is set to
appropriate position.
(b) Perform free running test in same manner as described
above, except with BATTERY CIRCUIT SELECTOR switch (S6, fig 2-2) set
to OFF.
NOTE
controlled by controlling the field current by use
of the field rheostat and operating the generator
at some speed below base speed. Since final adjust-
ment of voltage and speed may be necessary when the
generator is under load, care should be exercised
to prevent ceiling volts and specified field current
being exceeded when load is removed. FIELD CURRENT
0-5 AMPS (MAX) control (R27, fig 2-2) is rated at 5
amperes; therefore, DC AMMETER FIELD CURRENT meter
2-46