4-31. REMOTE BULB THERMOSTAT S3 TESTING AND REPLACEMENT.
This task covers:
a. Testing
b. Removal
c. Installation
INITIAL SETUP
Materials/Parts
Equipment Conditions
Lock Washers (5)
disconnected
Self Locking Nut
Control panel cover door raised and latched
Left side door open
Self Locking Nuts (2)
General Safety Instructions
Self Locking Nut
WARNING
Tie Down Straps
High voltage and exposed rotating parts are
Marker tags (2)
used m the refrigeration unit Personal injury
can result if power is connected
Silicone RTV
(1)
Be sure power has been disconnected at the source and remove two bolts (1) and lock washers (2) Open
control panel (3). Discard lock washers.
(2)
Remove screw (4) and cover (5).
(3)
Remove two bolts (6), lock washers (7), flat washers (8), and sensing bulb bracket (9) Discard lock
washers.
(4)
Remove self locking nut (10), lock washer (11), bolt (12), from sensing bulb bracket (9) Discard self
locking nut and lock washer.
(5)
Remove clamp (13)
Immerse sensing bulb (14) into a temperature controlled bath at 32F (0C). A bath at this temperature
(6)
can be made by putting the sensing bulb into a container of ice and covering with water. Ice must remain
packed around sensing bulb at all times during test
(7)
terminals 1 and 3 with thermostat setting at 24F (-4C) and at 40F (40 C). Continuity should be
indicated only when the setting is at 24F (-4C) If continuity was indicated at 400 F (4C) setting,
replace thermostat
(8)
If no failure was indicated, slip clamp (13) over sensing bulb (14).
4-69