TM 55-1925-282-14&P
0009 00
No Indication of Power
to the ROWPU
For ROWPU 1, check the condition of the REVERSE OSMOSIS
WATER MAKER No. 1 circuit breaker at 440V Power Panel No. 5.
Is
there any
For ROWPU 2, check the condition of the REVERSE OSMOSIS
No
indication of
WATER MAKER No. 2 circuit breaker at 440V Power Panel No. 5.
power at the
system
controller?
Is
Yes
the circuit
Reset the circuit breaker
breaker tripped as
Yes
by setting it to OFF,
indicated by the circuit
and then setting it
breaker being between
to the ON position.
the ON and OFF
positions?
No
Is the
Set the circuit
No
circuit breaker
breaker to the
in the ON
ON position.
position?
Yes
D From Sheet 2
Is any
indicator
Check the condition
No
illuminated at
of the applicable 24
the system
Vdc circuit breaker.
controller?
E
C
Yes
From Sheet 3
To Sheet 2
Is
Reset the
the circuit
circuit breaker
breaker tripped as
by setting it
Yes
indicated by the circuit
to OFF, and
breaker being between
then setting it
Does the high
the ON and OFF
to the ON
pressure pump run
Yes
positions?
position.
when the START switch is
pushed at the system
controller?
No
No
Is
No
Set the circuit breaker
the circuit
A To Sheet 3
to the ON position.
breaker
ON?
Yes
Exit
B To Sheet 3
Procedure 1. No Indication of Power to the ROWPU (Sheet 1 of 3)
0009 00-2