TM 9-4110-254-14
Table 4-1. Unit Preventive Maintenance Checks and Services for Model F5000RE
NOTE
If the equipment must be kept m continuous operation, do only the
procedures that can be done without disturbing operation. Make
complete checks and services when the equipment is shut down
Location
Item
Interval
Item to
Procedure
Not Fully Mission
Check/
Capable If:
Service
Refrigeration
Unit Exterior
1
Monthly
Doors/Cover
Service the doors and cover by lubricating the
a. Apply lubricating oil (MIL-L-2104) sparingly
from oil can onto the hinge moving joint
surfaces.
b. Wipe away excess lubricating oil with a
clean rag.
2
Grommet
Monthly
Check that grommet is m place and not cracked or
(Input Cable)
split. Replace if missing or damaged
3
Monthly
Barrel Bolts
Service the barrel bolts by lubricating them (fig.
a. Apply lubricating oil (MIL-L-2104) sparingly
from oil can onto the barrel bolt moving
joint surfaces.
b
Wipe away excess lubricating oil with a
clean rag.
4
Monthly
a. Inspect as much of coil as possible, without
coil
is
Coil
disassembly, for any evidence of
obstructed or evidence
refrigerant leak. If evidence of leak is
of leak is found
found, notify direct support maintenance to
repair or replace it as necessary
b. Inspect coil for obstructions If coil is
obstructed with dirt or fins are bent,
straighten fins as needed.
4-13