TM 9-4110-254-14
Table 4-1. Unit Preventive Maintenance Checks and Services for Model F5000RE - Continued
Location
Item
Interval
Item to
Procedure
Not Fully Mission
Check/
Capable If:
Service
Semi-
17
Repeat
Cycle
a. Check for loose or missing mounting
Mounting hardware or
Annually
Timer
socket hardware and wire terminals.
wire
terminals
are
Tighten or replace as necessary (para
loose.
Case
is
damaged.
b. Inspect case and mounting socket for
cracks, breaks, or evidence of overheating.
c.
Check and adjust the timer controls if
18
Semi-
Remote Bulb
a. Check for loose or missing mounting
Sensing bulb capillary
Annually
Thermostat
hardware and wire terminals Tighten or
line is kinked or broken.
Mounting hardware or
wire
terminals
are
b. Inspect for kinked or broken sensing bulb
loose.
capillary line If damaged, replace
c.
Install the circuit breaker cover onto the
Refrigeration
Unit Exterior
NOTE
The cover panel must be
removed for the following semi-
annual PMCS
19
Defrost
Semi-
Termination
Annually
Wire lead frayed or
Thermostat
broken.
Temperature
switch loose on tubing
loose.
b. Inspect for frayed or broken wire leads. If
damaged, repair or replace as needed
c.
Check that the switch is in contact with the
tubing. Tighten if loose.
4-20