TM 9-4110-254-14
b. Removal.
(1)
Be sure power has been disconnected at the source and remove two bolts (1), lock washers (2), flat
washers (3), and sensing bulb bracket (4). Discard lock washers.
(2)
Remove self locking nut (5), lock washer (6), bolt (7), and sensing bulb bracket (4). Discard self locking nut
and lock washer
(3) Remove clamp (8) from sensing bulb (9)
(4) Remove tiedown straps (12).
(5) Remove three self locking nuts (13), and screws (14). Discard self locking nuts.
(6) Remove thermometer (10), and any grommets (15) necessary to remove sensing bulb (9)
(7) Remove any silicone RTV remaining in grommets (15)
c.
Installation.
(1)
Install thermometer (10) routing sensing bulb (9) through grommets (15). Install any grommets removed
(2)
Install thermometer (10), three screws (14), and new self locking nuts (13).
(3)
Install tie down straps (12) as necessary.
(4)
Slip clamp (8) over sensing bulb (9).
(5)
Install clamps (8) and (11), bolt (7), new lock washer (6), and new self locking nut (5)
(6)
Install sensing bulb bracket (4), two flat washers (3), new lock washers (2), and bolts (1)
(7)
Apply silicone RTV into grommets (15) to seal evaporator enclosure.
NOTE
FOLLOW-ON MAINTENANCE
Unlatch and close control box cover door.
Close right side door.
Connect power and put unit back into service
4-105