TM 9-4110-255-14
Table 4-1. Unit Preventive Maintenance Checks and Services for Model F5000RD
NOTE
f the equipment must be kept in continuous operation, do only the procedures that can be done
I
without disturbing operation. Make complete checks and services when the equipment is shut
down.
he hourly intervals listed represent actual engine operation as indicated on the hourmeter.
T
Location
Item No.
Interval
Procedure
Not Fully Mission Capable If:
Item to
Check/
Service
Refrigeration
Unit Interior
NOTE
The refrigeration unit must be shut down
with the battery disconnected, the left side
door, and front door must be open for all of
the 8 hour PMCS.
1
8 Hours
Air Cleaner
Service the air cleaner by removing and cleaning
Air cleaner is missing or
it using compressed air.
clogged.
a.
b.
Open front door.
c.
Loosen clamp and remove air cleaner.
WARNING
Injury to personnel can result if compressed
air used for cleaning purposes exceeds
30 psig (207 kPa). When using compressed
air, wear safety glasses or goggles. Dirt can
be blown into your eyes.
d.
Using compressed air at 30 psig (207 kPa) or
less, blow dirt out of air cleaner.
e.
Install air cleaner and tighten clamp.
4-12