TM 9-4110-258-13
Table 4-1. Preventive Maintenance Checks and Services for Model F9000RE
NOTE
If the equipment must be kept in continuous operation, do only the procedures that can be done
without disturbing operation. Make complete checks and services when the equipment is shut
down.
Location
Item
Interval
Item to
Procedure
Not Fully Mission
No.
Check/
Capable If:
Service
Refrigeration
Unit Exterior
1
Monthly
Doors/Cover
Service the doors and cover by lubricating the
a. Apply lubricating oil (MIL-L-2104)
sparingly from oil can onto the hinge
moving joint surfaces.
b. Wipe away excess lubricating oil with a
clean rag.
2
Monthly
Barrel Bolts
Service the barrel bolts by lubricating them
a. Apply lubricating oil (MIL-L-2104)
sparingly from oil can onto the barrel bolt
moving joint surfaces.
b. Wipe away excess lubricating oil with a
clean rag.
3
Monthly
a.
Inspect as much of coil as possible, without
Coil
disassembly, for any evidence of
obstructed or evidence of
refrigerant leak. If evidence of leak is
leak is found.
found, notify direct support maintenance to
repair or replace it as necessary.
b.
Inspect coil for obstructions. If coil is
obstructed with dirt or bent fins, remove
or straighten fins as needed.
4-11