ARMY TM 9-4120-380-14
NAVY EE-000-BA-MMA-010/7053-AC
AIR FORCE TO 35E9-136-21
Electrical Data:
Power:
Input voltage.................................................................................................... 208 Vac, 3-phase, 50/60 Hz, 5-wire
Power consumption (total) ........................................................................................4.5 kW cooling, 8 kW heating
Continuous transients ........................................................................................ 10% voltage (187.2 to 228.8 Vac)
Fan Motors.
Type ...................................................................................................................... 3-phase, induction, ball bearing
Protection ................................................................................................................. Pilot break thermal overloads
Number of stages .......................................................................................................................................Two (2)
Type ........................................................................................................ 208 Vac, single phase, six (6) elements
Controls ................................................................................................................................................Thermostat
Safety switches................................................................................................................. High temperature cutout
Cooling:
Controls ................................................................................................................................................Thermostat
Safety switches.....................................................................................High and low refrigerant pressure and high
temperature cutouts, dirty filter switch
1.11
SAFETY, CARE AND HANDLING. Read and understand all instructions relating to the specific function you
are to perform before starting task.
1.11 1
Carefully read and understand all notes, cautions, and warnings contained in this manual that pertain to the
task you are to perform
1.11.2
Carefully read and understand all WARNING and CAUTION plates located on the air conditioner.
1.11.3
Never operate the air conditioner with any cover, air filter, or panel removed unless the instructions
specifically instruct you to do so Then do so only with extreme caution.
1.11.4
Carefully plan all maintenance tasks and never take unnecessary risks.
1-7