TM 9-4120-399-14
5-22. LIQUID SIGHT INDICATOR (SIGHT
GLASS).
This Task Covers:
b. Installation
a. Removal
Initial Setup:
Tools Required
Tool kit, Refrigeration
Material's Rewired
None
Equipment Condition
Air conditioner shut down and cool.
Removal.
(1) Remove two screws (1), two flat washers (2), and two lock washers (3) that secure
liquid sight indicator (4) and mounting plate (5) to casing (6).
(2) Remove liquid sight indicator (4) and mounting plate (5) from casing (6).
b. Installation.
NOTE
Do not disassemble liquid sight indicator.
(1) Position liquid sight indicator (4) on tubing.
(5) Leak test all newly connected joints and those in the repair area (See para. 5-10).
(8) Secure mounting plate (5) and liquid sight indicator (4) to casing (6) with two screws
(1), two flat washers (2), and two lock washers (3).