TM
9-4120-401-14
5 - 2 2 . REFRIGERANT DESICCANT DEHYDRATOR (FILTER-DRIER). - continued
b. Replace.
(1) Remove four screws (2) and two mounting clamps (3).
(2) Disconnect two flare nuts (4) and remove refrigerant desiccant dehydrator (1) from unit.
Replacement refrigerant desiccant dehydrators are packaged with sealing caps
on the flare fittings to prevent moisture contamination of the desiccant filtering
media. Remove these caps immediately prior to installation. Never install a
refrigerant desiccant dehydrator from which caps have been removed for an
extended or unknown period of time.
(3) Connect two flare nuts (4) to each end of refrigerant desiccant dehydrator (1).
(4) Install two mounting clamps (3) on refrigerant desiccant dehydrator (1) and aline mounting holes.
Secure with four screws (2).
NOTE
FOLLOW-ON MAINTENANCE:
5-56