TM 9-4120-403-14
Figure 5-19. Condenser Coil (C)
Replacement
(1) Observe position of tubing from condenser for ease of reassembly.
(2) While purging the system with nitrogen, debraze the remaining tube joints to the condenser. (See paras 5-7
and 5-8.)
(4) Using gloves to protect your hands and coil fins, carefully slip the coil from the unit.
(5) Align condenser coil and guard and secure with four screws and washers.
(6) While purging the system with nitrogen, braze the tubejoints in positions noted at disassembly. (See paras 5-8
and 5-9.)
5-65