TM 9-4120-404-14
(8) Operates in environmental conditions from tropic to arctic.
(9) Is fully portable.
(10) Designed for low-noise level operation.
c. Special features.
The control panel may be removed from the unit and remote mounted.
1-10. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS. (Refer to
Figure 1-2.)
(1) Fresh Air Filter -- Provides filtered outside air.
(2) Condenser Air Outlet Guard --
Protects personnel from injury and fans from damage.
(3) High Pressure Cutout Switch --
This switch is
factory set to
shut off the compressor if
the refrigerant
discharge line pressure rises to 480 + 10 psig (33.75 + .7 kg/cm 2) (4) Low Pressure Cutout Switch -- This
switch is factory set to shut off the compressor if the refrigerant suction line pressure drops to 15 + 3 psig
(1.05 + .2 kg/cm 2).
(5) Refrigerant Sight Glass (liquid sight indicator) -- Allows visual inspection and indicates condition of
liquid refrigerant when the unit is operating in the cool mode. A moisture indicator in sight glass indicates
(6) Condenser Coil --
Serves as a
heat exchanger by
transferring heat from the refrigerant passing through
the tubing to the air passing over the tubing and fins.
(7) Evaporator Fan Assembly --
Draws air into the evaporator section and exhausts it
through the evaporator
(cooling) coil and heater elements and into the room or enclosure.
(8) Evaporator Coil --
Serves as a
heat exchanger by
transferring heat from the air passing over the tubing
and fins to the refrigerant passing through the tubing.
(9) Fabric Cover -- Shown in stowed (operational) position. When rolled down and snapped it protects the
rear (exposed) surface of the unit.
(10) Heater Elements --
Consists of
six 1470 watt heating elements.
1-3