TM 9-4120-404-14
1-11. EQUIPMENT DATA. Refer to
Table 1-1. for the performance data for this air conditioner.
Table 1-1. Equipment Data.
OPERATING TEMPERATURES
LOW ...................................................................................................... -50 F(-45 C)
HIGH ..................................................................................................+120 F (+49 C)
PERFORMANCE
COOLING CAPACITY .............................................................................. 36,000 Btu/hr
HEATING CAPACITY .............................................................................. 31,200 Btu/hr
POWER REQUIRED
VOLTAGE ......................................................................................................208 VAC
PHASE ..................................................................................................................... 3
HERTZ ................................................................................................... 50, 60, or 400
FULL LOAD AMPERAGE (Amperage reading is the average
of the three phases)
50 Hz, 60 Hz, or 400 Hz .........................................................45 amps maximum
DIMENSIONS
WIDTH .............................................................................................. 38.0 in. (78.1 cm)
DEPTH .............................................................................................. 35.0 in. (54.6 cm)
HEIGHT .......................................................................................... 27.0 in. (140.6 cm)
WEIGHT .....................................................................................420 pounds (190.9 kg)
REFRIGERANT
TYPE ...................................................................................................................R-22
CHARGE ......................................................................................... 11 pounds (4.9 kg)
OIL TYPE ...................................................................................................... BB-L-825
INITIAL ...............................................................................................................55 oz.
RECHARGE .......................................................................................................52 oz.
AIRFLOW
AIR FILTER .............................................................................. Permanent - Re-usable
RATE (At 0.25 water gauge) .......................................................................... 1,340 cfm
1-8