TM 9-4120-404-14
3-11. ALTERNATE INPUT POWER CABLE CONNECTOR (J8) LOCATIONS . If input power cable connection is to be
relocated to the alternate location at the rear of the unit, perform the following steps. (Refer to Figure 3-4).
WARNING
Voltages used can kill. Always disconnect power cord to air conditioner before
performing any internal maintenance. Shutting unit off at its control panel does
not disconnect unit power.
a. Remove fourteen screws (1) and rear panel (2).
b. Remove plug P15 from connector J15 located on EMI filter assembly FL1 (3).
c. Remove plug P15A from dummy plug.
d. Install plug P15A into connector J15 on EM filter assembly FL1 (3).
e. Install plug P15 onto dummy plug.
f. Remove cap assembly from input power connection J8 on rear of unit and connect unit to 208 VAC, 3 phase,
50/60/400 Hz power.
g. Install rear panel (2) and fourteen screws (1).
Figure 3-4. Alternate Input Cable Connector (J8) Locations.
3-13