TM 9-4120-404-14
3-35. LOUVER ACTUATOR CABLES. - Continual
(4) Place eyelet end of cables into position in louver assemblies and install two screws (6) and two nuts (7).
(5) Compress and remove two clamps (8) on louver actuator cables (4) and (5) and insert plain cable end
through control bracket (9) and into bracket on louver actuator, (6) Loosely install two mechanical posts (3) onto ends of
louver actuator cables (4) and (5).
(7) Loosely install cable clip (2) and screw (1) to hold louver actuator cables (4) and (5).
(8) Loosely install cable ties (14) to hold louver actuator cables (4) and (5) in place within unit housing as
needed.
d. Adjustment
CAUTION
The louver actuator cables must be adjusted when air conditioner is shut down
and cool If cables are adjusted while unit is not completely cool, cables may be
damage to unit and improper operation of air conditioner may occur.
(1) Position the blades of both louver assemblies to a fully closed position.
(2) Compress and position clamps (10) together until both clamps are hard against the angle (11) on the
(3) Loosen clamps (8) at control bracket (9) to allow louver actuator cables (4) and (5) to be easily moved int o
the bracket on the louver actuator cylinder (15).
(4) Slide the mechanical posts (3) on each louver actuator cable down each cable until the post is hard against
the bracket on the louver actuator cylinder (15).
(5) Tighten both mechanical posts (3) on both louver actuator cables (4) and (5).
(6) Compress and slide four clamps (8) on louver actuator cables (4) and (5) until each clamp is hard against
control bracket (9).
(7) Tighten screw (1) to secure louver actuator cable (4) and (5) against the cable mounting bracket (17).
(8) Tighten all cable ties (14) as required.
3-84