Table 4-4. Wire List - Continued
TERMINATION
TERMINATION
AWG WIRE
LENGTH
SIZE
FROM
TERMINAL TYPE
TO
TERMINAL TYPE
IN
CM
S8-6
HR3-B
13216E6191-1(97403)
12 AWG-WHT
60.00
152.40
K5A-NO
K2-A1
18 AWG-WHT
24.00
60.96
TM1-9
K5A-C
18 AWG-WHT
24.00
60.96
NOTE
1
Type SO Cable, Conductor Size 12-4, 20 Amps Minimum Rating 250 Vac.
2
Type SO Cable, Conductor Size 14-4, 15 Amps Minimum Rating 250 Vac.
c.
Removal..
(1) Tag and disconnect wire lead(s) from component.
(2) Remove tiedown straps and loosen clamp(s) as necessary to remove wire(s).
(3) Remove any silicone RTV remaining in evaporator frame grommets (3).
d.
Installation..
(1) Carefully route wire lead(s) through clamp(s) and grommet(s) as necessary.
(2) Connect wire lead(s) to component using tags and wiring diagram (fig. 1-4). Remove tags.
(3) Install tiedown straps as necessary and tighten any clamp(s) that were loosened for removal.
(4) Apply silicone RTV into evaporator frame grommets (3) to seal evaporator enclosure.
(5) Close control box cover (2). Install six screws (1).
NOTE
FOLLOW-ON MAINTENANCE:
Unlatch and close control box cover door.
Connect power and put unit back into service.