3-2. USE OF TABLE - Continued
TABLE 3-1. TROUBLESHOOTING (cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4. COMPRESSOR STARTS NORMALLY, BUT COMPRESSOR CIRCUIT BREAKER SOON TRIPS. (COOLING
STOPS.)
Step 1. Check to be sure fabric cover is rolled up.
Roll and secure fabric cover.
Step 2. Check to be sure condenser air inlet and outlets are not obstructed.
Remove obstructions. On models F36T-2SA and F36T4-2SB the Condenser.
Discharge air deflector door must be open.