TM 9-4120-370-14
TO 35E9-229-1
TABLE 3-1. TROUBLESHOOTING (cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 3. Check to be sure that condenser fans are operating. (Air being discharged from condenser air outlets.)
Reset compressor circuit breaker and restart in COOL mode.
If condenser fans do not operate immediately, turn selector switch to OFF and
contact unit maintenance.
5. COMPRESSOR STARTS NORMALLY, BUT HIGH OR LOW CUTOUT SWITCH SOON TRIPS. (COOLING
STOPS.)
Step 1. Check to be sure fabric cover is rolled up.
Roll and secure fabric cover.