TM 9-4120-371-14
c. Installation
(1)
Using screwdriver, secure control panel to junction box with four screws.
CAUTION
Take care that sensing bulb capillary line is not kinked and that bulb and
capillary are not cut or damaged during installation.
(2)
Carefully feed sensing bulb and capillary up and into conditioned air intake compartment. (See fig.
(3)
Using screwdriver, secure remote sensing bulb with clamp, flat washer, lock washer, and screw.
(4)
Install grommet in bulkhead.
(5)
Coil excess capillary tubing in recess behind control panel.
(6)
Connect P7 plug and harness to receptacle J7 on the control panel.
(7)
Carefully move junction box into position and aline mounting hardware.
(8)
Using screwdriver, tighten four captive panel screws in junction box mounting flanges.
(9)
Using screwdriver, secure filter and filter retainer with two captive turnlock stud fasteners.
(10) Using screwdriver, secure intake grille assembly with six captive turnlock stud fasteners.
(11 ) Set the bottom of the lower front panel in position so that the flange is inside the lip on the cabinet
base.
(12) Push the top of the lower front panel back into position.
(13) Using screwdriver, secure lower f rent panel to casing with two captive panel fastener screws.
Follow-on procedure: Connect power.
4-82