TM9-4120-400-14
4-5. INSTALLATION INSTRUCTIONS. - continued
(6) Fabricate an input cable of required length using the MS3106R18-11S connector supplied with air
conditioner for connection to J1 or J11. (See chart below and figure 4-4 Sheet 7.) If J11 connector is
used, be sure the wiring to TB3 terminal board is relocated in accordance with paragraph 4-5 a.
F9000H-1SA
F9000H-3SA
Pin
Internal wiring connection
Pin
Internal wiring connection
J1 andJ11
J1 and J11
115 volt
A
A
Phase A
Neutral
B
B
Phase B
Blank (not used)
C
Phase C
C
D
Ground
D
Ground
Blank (not used)
E
E
Blank (not used)
(7) Remove the condensate drain plug from lower left rear comer of the unit. If air conditioner is mounted
in a location where water pouring from this drain will be objectionable or create a hazard, connect a
drain line at this point. The fitting used must have a male 1/8 -27 NPT connection to unit. Hose, rigid
pipe or tubing can be used to direct drain water to a more desirable disposal location.
(8) Connect power cable to input power source (F9000H-3SA to 208 volt, 3 phase, 50/60 hertz or
F9000H-1SA to 115 volt, single phase, 50/60 hertz) and air conditioner.
NOTE
For more information on air conditioner installations, refer to MIL-HDBK-116
Environmental Control of Small Shelters.
4-22