TM9-4120-400-14
4-4. SERVICE UPON RECEIPT OF MATERIAL. - CONTINUED
NOTE
The unit weight (less shipping pallet) is 190 pounds (86.2 kg) for the F9000H-3SA and
172 pounds (78.0 kg) for the F9000H-1SA. When lifting or moving the unit on the
shipping pallet, a forklift maybe used. When lifting the unit into position use four people,
one at each lifting handle.
(4) Remove Pallet. Tilt the unit and pallet or raise the unit using a forklift. Remove the four bolts from the
bottom of the pallet. Using 4 people (one at each lifting handle), carefully lift the unit from the shipping
pallet.
INSTALLATION
INSTRUCTIONS.
a. Air Conditioner Preparation For Installation.
(1) Two input power connectors are provided on the air conditioner. (See fig. 4-1.) Connector J1 is
located on the front of the air conditioner above the control panel module. ConnectorJ11 is located
on the rear of the air conditioner in the upper left corner. Determine which connector best suits your
installation. If power source is inside of conditioned area use J1. If power source is outside of
conditioned area use J11.
(a) Air conditioners are shipped from the factory wired for the use of the J1 power connector. If this
connector is used no change is necessary. (See fig. 4-2.)
(b) If the J11 connector is to be used on the F9000H-3SA, leads TB1-1- -TB3-1, TB1-2- -TB3-2, and
TB1-3- -TB3-3 on terminal board TB3 must be moved from terminals 1, 2, and 3 to terminals 4, 5,
and 6 respectively. If the J11 connector is to be used on the F9000H-1SA, leads TB1-1- -TB3-1
and TB1-2- -TB3-2 on terminal board TB3 must be moved from terminals 1 and 2 to terminals 4
and 5 respectively. Proceed as follows:
1 Remove top front (evaporator section) panel from air conditioner.
2 Disconnect wire TB1-1--TB3-1 from TB3 terminal 1 and reconnect to terminal 4.
3 Disconnect wire TB1-2--TB3-2 from TB3 terminal 2 and reconnect to terminal 5.
4
(F9000H-3SA only) Disconnect wire TB1-3--TB3-3 from TB3 terminal 3 and reconnect to
terminal 6.
Connectors are provided to permit remote installation of the control module. To install the control
(2)
module in a remote location (within the conditioned space) the following steps must be taken. (See
(b) Loosen sensing bulb clamp screws and slip sensing bulb out of clamps.
(c) Loosen control module mounting screw and carefully pull control module out of unit. Use care to
avoid damage to sensing line.
(d) Carefully work sensing bulb through frame and out of the unit.
4-8