TM 9-4120-402-14
5-5. OUTSIDE COVERS AND PANELS.
This task covers: a. Repair
b. Replace
INITIAL SETUP
Tools
Materials/Parts
Refrigeration Unit Service Tool Kit
Adhesive
Gloves
Adhesive Remover
Brush
Gasket
NOTE
The only authorized repairs are replacement of gaskets.
a.
Repair.
(1) Use only gaskets, insulation, or name plates identified in TM 9-4120-402-24P.
(2) Remove as much old gasket or insulation material as possible by pulling or scraping it away from the metal
surface.
WARNING
Adhesive remover is flammable and the vapors can be explosive. Keep away from sparks or
flame.
Repeated or prolonged skin contact or inhalation of vapors can be toxic. Use in a well ventilated
area and wear gloves.
(3)
Soften and remove old adhesive and gasket residue, using adhesive remover and a stiff brush.
(4)
See Appendix F to identify and fabricate gasket or insulation to be replaced using material specified.
(5)
Coat mating surfaces of metal and gasket with adhesive. Let both surfaces air dry until adhesive is tacky but
will not stick to fingers.
(6)
Starting with an end, carefully attach gasket to the metal. Press into firm contact all over.
(7)
Minor dents and bent edges can be straightened using common sheet metal repair procedures.
(8)
Should touch up or refinishing be necessary, see TM 43-0139.
b.
Replace.
Replace panels that are badly dented, bent, or punctured.
5-10