TM 9-4120-407-14
3-37. CONDENSER FANS AND MOTOR TESTING AND REPLACEMENT. (Cont)
NOTE
Support or hold motor in place. Note number and location of shims as
mounting hardware is removed.
(4) Remove one self locking nut (1) Figure 3-57, flat washer (2), screw (3), flat washer (4), wire
lead (5), flat washer (6), and lock washer (7). Discard self locking nut and lock washer.
Motor must be supported as hardware is removed or damage to the
motor will occur.
(5) Remove three self locking nuts (8), flat washers (9), screws (10) and four shuns (11). Carefully
remove motor (12) from left side of air conditioner.
c. Installation.
(1) Lift motor (12) Figure 3-57, into position and install four shims (11), three screws (10), flat
washers (9), and new self locking nuts (8).
(2) Install screw (3), flat washer (4), wire lead (5), flat washer (6), new lock washer (7), flat
washer (2) and new self locking nut (1).
(3) Install inlet bell (8) Figure 3-56, six screws (6), and flat washers (7).
3-128