TM 9-2330-227-14&P
ORGANIZATIONAL TROUBLESHOOTING - CONTINUED
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
8. ALL RECEPTACLES DO NOT WORK - CONTINUED
Step 7.
contact of left main circuit breaker and black probe on the other.
If multimeter reads no continuity, replace circuit breaker
Repeat step 7 for right main circuit breaker.
Step 8.
If receptacles still do not work, wire leading from left
main circuit breaker, to place where wall receptacles splice
in, needs to be replaced. Notify Direct Support Maintenance.
9. ONE OR MORE, BUT NOT ALL RECEPTACLES WILL NOT WORK
Check junction boxes to make sure all circuit breakers are on.
Step 1.
NOTE
If all receptacles are out on one side, do the following steps. If not, go to step 4.
Unplug power source.
Step 2.
contact of branch circuit breaker which controls receptacles
and black probe on the other contact.
If multimeter reads no continuity, replace circuit breaker
Step 3.
end of wire leading from branch circuit breaker which
controls receptacles to the first receptacle and black probe
on the other end.
If multimeter reads no continuity, notify Direct Support
Maintenance.