TM 9-4110-255-14
Table 2-1. Operator Preventive Maintenance Checks and Services for Model F5000RD - Continued
Location
Item No.
Interval
Procedure
Not Fully Mission Capable If:
Item to
Check/
Service
33
b.
Inspect the starting motor for frayed or
Wire leads are frayed or
Cont
broken wire leads. If damaged, notify unit
broken.
maintenance to repair or replace it as
necessary.
34
Weekly
Voltage
a.
Inspect voltage regulator for any evidence of
Voltage regulator shows
Regulator
overheating such as discoloration of casing
evidence of overheating.
or burn marks.
b.
Inspect the voltage regulator for frayed or
Wire leads are frayed or
broken wire leads. If damaged, notify unit
broken.
maintenance to repair or replace it as
necessary.
WARNING
Muffler may be hot to touch and can
cause serious personal injury. Allow
muffler to cool.
35
Weekly
Muffler,
Hole in muffler, exhaust
Exhaust Pipes, dents and missing or damaged clamps.
pipes or clamps missing
and Clamps
or loose.
Refrigeration
Unit Exterior
36
Monthly
Doors/Cover
a.
bottom doors, and control box cover for any doors do not stay closed.
cracks, tears, and loose or missing hardware.
If cracked, notify direct support
maintenance for repair. If hardware is loose
or missing, notify unit maintenance to
tighten or replace as necessary.
b.
Inspect the doors and cover for any chipped
or missing paint and evidence of corrosion.
If paint is damaged or shows evidence of
corrosion, notify direct support maintenance
to paint it.
c.
Inspect the hinges for smooth operation and
loose or missing attaching hardware. If
hinges bind, notify unit maintenance to
lubricate them. If attaching hardware is
loose or missing, notify direct support
maintenance to replace it.
2-18