TM 9-4110-256-14
Figure 4-40. Refrigeration System Pump Down
4-46.
LONG TERM STORAGE OR SHIPMENT.
Placement of equipment in long term storage should be for extended periods of time (45 days or more).
a. Before placing the equipment in long term storage, current preventive maintenance checks and services should
be completed, shortcomings and deficiencies should be corrected, and all Modification Work Orders (MWO)
should bet applied.
b. Open both side condenser doors and both front bottom doors.
c.
Loosen four compressor mount locknuts (1, fig. 4-41). Tighten four screws (2) just to the point where shipping
bracket (3) cannot be removed from spring (4). Tighten four locknuts.
4-96