TM 9-4110-258-13
4.40 THERMOMETER TESTING AND REPLACEMENT. - Continued
b. Removal.
(1) Be sure power has been disconnected at the source and open left side door.
(2) Remove screw (1), lock washer (2), and flat washer (3). Discard lock washer.
(3) Remove clamp (4).
(4) Remove tie down straps (8).
(5) Remove three bolts (9) and lock washers (10). Discard lock washers.
(6) Remove thermometer (6) and any grommets (11) necessary to remove sensing bulb (5).
(7) Remove any silicone RTV remaining in evaporator frame grommet (11).
c. Installation.
(1) Install thermometer (6) routing sensing bulb (5) through grommets (11). Install any grommets removed.
(2) Install three new lock washers (10) and bolts (9).
(3) Slip clamp (4) over sensing bulb (5).
(4) Install clamps (4) and (7), flat washer (3), new lock washer (2), and screw (1).
(5) Install tie down straps (8) as necessary.
(6) Apply silicone RTV into evaporator frame grommet (11) to seal evaporator enclosure.
(7) Close left side door.
NOTE
FOLLOW-ON MAINTENANCE:
Connect power and put unit back into service