TM9-4120-398-14
TABLE 4-2. UNIT TROUBLESHOOTING-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 5. Check for tripped thermal cutout (TCO) in fan motor.
If problem still exists, refer to supervisor.
AIR CONDITIONER STOPS - AUTO MODE.
3.
Step 1. Check for tripped circuit breaker.
Step 2. Check for defective mode selector switch (S1.)
Step 3. Check for defective thermostat control switch (S2 )
Step 4. Check for defective control relay (K4, K5.)
Step 5. Check for continuity in high temperature cutout switch.
If problem still exists, refer to supervisor.
NO (OR REDUCED) COOLING.
4.
Step 1. Check sight gIass for bubbles or discoloration.
Shut down air conditioner and contact supervisor.
Step 2. Check for defective time delay relay (K6).
4-14