TM9-4120-398-14
TABLE 4-2. UNIT TROUBLESHOOTING-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
7.
MOTOR/COMPRESSOR UNIT INOPERATIVE (OTHER COMPONENTS FUNCTIONING).
Step 1. Check for defective time-delay relay (K6.)
Step 2. Check for defective motor starter (K3.)
If problem still exists, refer to supervisor.
8.
EVAPORATOR BLOWER INOPERATIVE - VENT MODE OR AUTO MODE.
Step 1. Check for broken belt
Step 2. Check for pulley loose on motor shaft or on blower shaft.
Step 3. Check for defective mode selector switch (S1).
Step 4. Check for defective control relay (K4, K5.)
Step 5. Check for defective motor starter (K1.)
Step 6. Check for defective evaporator fan motor (B1.)
If problem still exists, refer to supervisor.
9.
Check for defective high temperature cutout switch.
If problem still exists, refer to supervisor.
4-16