TM9-4120-398-14
TABLE 4-2. UNIT TROUBLESHOOTING-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
10.
Step 1. Check for loose impeller.
Step 2. Check for defective mode selector switch (51).
Step 3. Check for defective control relay (K4-K5).
Step 4. Check for defective motor starter (K2.
Step 5. Check for defective condenser fan motor (B2).
If problem still exists, refer to supervisor.
11.
Step 1. Check for defective thermostat (S2).
Step 2. Check for defective motor starter (K3.
Step 3. Check sight glass for bubbles or discoloration.
Shut down air conditioner and contact supervisor.
4-17